null
Ireland EU online store
Victron Energy

Victron Energy AGM Super Cycle Batteries

MPN:
BAT412015080
Special Offer
  • 38Ah Victron Super Cycle AGM Battery
  • Victron Super Cycle AGM Battery with M8 Bolt
  • 60Ah Victron Super Cycle AGM Battery
  • 100Ah Victron Super Cycle AGM Battery
  • 125Ah Victron Super Cycle AGM Battery
  • 170Ah Victron Super Cycle AGM Battery
  • 230Ah Victron Super Cycle AGM Battery
$49.14 - $680.30

Description

The AGM range has very low internal resistance making them particularly suitable for high current discharge applications such as for inverters, thrusters and winches. 

VRLA AGM: design life 7-10 years

A truly innovative battery

The AGM Super Cycle batteries are the result of recent battery electrochemistry developments.
The paste of the positive plates is less sensitive to softening, even in case of repeated 100% discharge of the battery, and new additives to the
electrolyte reduce sulfation in case of deep discharge.

Exceptional 100% depth of discharge (DoD) performance

Tests have shown that the Super Cycle battery does withstand at least three hundred 100% DoD cycles.
The tests consist of a daily discharge to 10,8V with I = 0,2C₂₀, followed by approximately two hours rest in discharged condition, and then a recharge with I = 0,2C₂₀. The two hours rest period in discharged condition will damage most batteries within 100 cycles, but not the Super Cycle battery.

Victron recommend the Super Cycle battery for applications where an occasional discharge to 100% DoD, or frequent discharge to 60-80% DoD is expected.

Smaller and lighter

An additional advantage of the new chemistry is a slightly smaller size and less weight compared to our standard deep cycle AGM batteries.

Low internal resistance

The internal resistance is also slightly lower compared to our standard deep cycle AGM batteries.

Cycle life

≥ 300 cycles @ 100% DoD (discharge to 10,8V with I = 0,2C₂₀, followed by approximately two hours rest in discharged condition, and then a recharge with I = 0,2C₂₀)
≥ 700 cycles @ 60% DoD (discharge during three hours with I = 0,2C₂₀, immediately followed by recharge at I = 0,2C₂₀)
≥ 1000 cycles @ 40% DoD (discharge during two hours with I = 0,2C₂₀, immediately followed by recharge at I = 0,2C₂₀)

Effect of temperature on charging voltage

The charge voltage should be reduced with increased temperature. Temperature compensation is required when the temperature of the battery is
expected to be less than 10°C / 50°F or more than 30°C / 85°F during long periods of time.
The recommended temperature compensation for Victron VRLA batteries is -4 mV / Cell (-24 mV /°C for a 12V battery).
The centre point for temperature compensation is 25°C / 70°F.

Victron Energy AGM Super Cycle Battery Datasheet

View AllClose